Approved by ISIB
(Institut de Securite
Incendie - Belgium)
FIRECEL SR 125 RF1 are designed, manufactured and tested as data transmission cables for emergency services. These are used for data and voice transmission when high frequency signal has to be assured also in the event of a fire.
-40°C to +90°C
10 times the outer diameter.
| Single pair | white - blue |
| Multipair | white - blue numbered |
| Fire resistant | NBN C 30-004 (cat. F3) / NBN 713-020 (RF1) / EN 50200 (PH90) / IEC 60331-23 |
| Fire retardant | NBN C 30-004 (cat. F2) / EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C) |
| Flame retardant | NBN C 30-004 (cat. F1) / EN 60332-1-2 / IEC 60332-1-2 |
| Acid gas emission | EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2 |
| Smoke density | EN 61034-2 / IEC 61034-2 |
Solid plain annealed copper wire.
High performance fire resistant silicone rubber.
Insulated cores are twisted to form pairs.
Two-pair cable had four cores laid in quad formation.
Three pairs are cabled together.
Glass tape.
Aluminium/polyester tape with tinned copper drain wire.
LSZH thermoplastic material.
Colour orange (other colours on request).