firecel
Home » Prodotti » Cavi resistenti al fuoco » FIRECEL SR 116H

FIRECEL SR 116H

  • R-SR/LSZH 450/750 V
     

Applications

FIRECEL SR 116H are designed, manufactured and tested for general application in power supply and signal wiring, for emergency circuit and fire circuit control.

Operating temperature

-40°C to +90°C
(for insulated conductors only: max 200°C).

Minimum bending radius

10 times the outer diameter.

Colour code to HD 308


Without earth conductor

2 cores blue - brown
3 cores brown - black - grey
4 cores blue - brown - black - grey
5 cores blue - brown - black - grey - black


With earth conductor

3 cores yellow/green - blue - brown
4 cores yellow/green - brown - black - grey
5 cores yellow/green - blue - brown - black - grey

Applicable Standards

Fire resistant CEI 20-36/2-1 / EN 50200 (PH90) / IEC 60331-21
Flame retardant EN 60332-1-2 / IEC 60332-1-2
Fire retardant EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C)
Acid gas emission EN 50267-2-1 / IEC 60754-1
EN 50267-2-2 / IEC 60754-2
Smoke density EN 61034-2 / IEC 61034-2

Cable construction

Conductors

Plain annealed copper wire, stranded according to EN 60228 class 2.

Insulation

High performance fire resistant silicone rubber.

Cabling

Insulated cores are cabled together.

Outer sheath

LSZH thermoplastic material.
Colour red (other colours on request).