FIRECEL SR 109 are designed, manufactured and tested for general application in power and signal wiring, for emergency circuit and fire circuit control where high rejection to electrostatic noise is needed.
-40°C to +90°C
8 times the outer diameter.
Without earth conductor
| 2 cores | blue - brown |
| 3 cores | brown - black - grey |
| 4 cores | blue - brown - black - grey |
| 7 cores and above | black numbered |
With earth conductor
| 3 cores | yellow/green - blue - brown |
| 4 cores | yellow/green - brown - black - grey |
| 5 cores | yellow/green - blue - brown - black - grey |
| 7 cores and above | yellow/green - black numbered |
| Fire resistant | CEI 20-36/2-1 / EN 50200 (PH120) / IEC 60331-21 |
| Flame retardant | EN 60332-1-2 / IEC 60332-1-2 |
| Fire retardant | EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C) |
| Acid gas emission | EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2 |
| Smoke density | EN 61034-2 / IEC 61034-2 |
Plain annealed copper wire, flexible according to EN 60228 class 5.
High performance fire resistant silicone rubber.
Insulated cores are cabled together.
Aluminium/polyester tape with tinned copper drain wire.
LSZH thermoplastic material.
Colour red (other colours on request).