Power supply and signals trasmission, indoor or outdoor even wet environment.
For fixed laying in free air, in pipe or conduit, on masonry and metal structures or suspended.
In places where in case of fire people are exposed to serious risks for emission of smoke, toxic and corrosive gases and where you want to avoid damage to facilities, equipment, goods.
Suitable for feeding of: emergency exits, alarm signals, warning of smoke or gas, escalators.
Suitable for laying underground direct or indirect.
-40°C to +90°C
(for insulated conductors only: max 200°C).
10 times the outer diameter.
Without earth conductor
| 2 cores | blue - brown |
| 3 cores | brown - black - grey |
| 4 cores | blue - brown - black - grey |
| 5 cores | blue - brown - black - grey - blackblack - blue |
With earth conductor
| 3 cores | yellow/green - blue - brown |
| 4 cores | yellow/green - brown - black - grey |
| 5 cores | yellow/green - blue - brown - black - grey |
| Fire resistant | EN 50200 (PH90) / EN 50362 (PH90) / IEC 60331-21 / BS 6387 (cat. C-W-Z) / SS 299 part 1 |
| Flame retardant | EN 60332-1-2 / IEC 60332-1-2 |
| Fire retardant | EN 50266-2-4 (cat. C) / IEC 60332-3-24 (cat. C) |
| Acid gas emission | EN 50267-2-1 / IEC 60754-1 EN 50267-2-2 / IEC 60754-2 |
| Smoke density | EN 61034-2 / IEC 61034-2 |
Plain annealed copper wire, stranded class 2 for section up to 10 mm2 or flexible class 5 for section above 10 mm2 according to EN 60228.
High performance fire resistant silicone rubber.
Insulated cores are cabled together.
Extruded LSZH thermoplastic material.
Colour red (other colours on request).