Can be used in cable tray or conduit to connect electrical instrumentation and communication circuits in industrial process controls, refineries, oil and gas plant. Excellent protection against corrosion, humidity and poor vibration resistance.
-20 °C to +80 °C (for general use);
-40 °C to +90 °C (on request).
20 times the outer diameter.
| BS 5308 or EN 50288-7 |
Basic design |
| IEC 60332-1 | Flame retardant |
| IEC 60332-3 | Fire retardant (cat. C or A according to requirements) |
| IEC 60754-1 | Halogen free properties (only for LSZH cables) |
| IEC 61034-2 | Low smoke emission (only for LSZH cables) |
Tinned conductors.
Single triad or multitriads.
Galvanized steel tape armour (GSTA).
Different insulation and sheath colours.
Sheath materials can be provided for excellent water, oil, hydrocarbons, UV resistance or other special performance.
Plain annealed electrolytic copper wire according to EN 60228 class 1(U) solid, class 2 (R) stranded, class 5 (F) flexible.
PVC, PE, XLPE or LSZH thermoplastic material.
The insulated cores shall be twisted in pairs for a good reduction of the electromagnetic noise.
Aluminium/polyester tape, coverage >100%, aluminium in contact with tinned copper drain wire.
The screened pairs are cabled with suitable non hygroscopic fillers (when necessary) and wrapped with polyester tape if required.
Aluminium/polyester tape, coverage >100%, aluminium in contact with tinned copper drain wire.
PVC or LSZH thermoplastic material.
Lead alloy.
PE, PVC or LSZH thermoplastic material.
Single layer of galvanized steel wires (SWA).
PVC or LSZH thermoplastic material.