not armoured
armoured
Can be used in cable tray or conduit to connect different types of thermocouple in industrial process controls, refineries, oil and gas plants.
-20 °C to +80 °C (for general use);
-40 °C to +90 °C (on request).
Not armoured type:
12 times the outer diameter (for conductors class 1 and class 2);
10 times the outer diameter (for conductors class 5).
Armoured type:
15 times the outer diameter.
| BS 5308 or EN 50288-7 |
Basic design |
| IEC 60332-1 | Flame retardant |
| IEC 60332-3 | Fire retardant (cat. C or A according to requirements) |
| IEC 60754-1 | Halogen free properties (only for LSZH cables) |
| IEC 61034-2 | Low smoke emission (only for LSZH cables) |
Calibration and colours according to BS - DIN - NF - UNI.
Stranded conductors.
Galvanized steel wire braid (GSWB) or galvanized steel tape armour (GSTA).
Sheath materials can be provided for excellent water, oil, hydrocarbons, UV resistance or other special performance.
Solid alloy.
ANSI MC 96.1 or IEC 60584-3.
PVC, PE, XLPE or LSZH thermoplastic material.
The insulated cores shall be twisted in pairs/triads for a good reduction of the electromagnetic noise.
Aluminium/polyester tape, coverage >100%, aluminium in contact with tinned copper drain wire.
The screened pairs are cabled with suitable non hygroscopic fillers (when necessary) and wrapped with polyester tape if required.
Aluminium/polyester tape, coverage >100%, aluminium in contact with tinned copper drain wire.
PE, PVC or LSZH thermoplastic material.
Single layer of galvanized steel wires (SWA).
PVC or LSZH thermoplastic material.